Model No: YeM6PV
YeM6PV DC molded case circuit breaker
YeM6PV DC molded case circuit breaker is used in DC distribution networks with rated operating voltage up to DC1000V
(4P) and rated current up to 250A .
Used to distribute electrical energy and protect lines and power equipment from damage
caused by overload, short circuit, and other faults.
This circuit breaker can be installed vertically or horizontally.
Standard:IEC/EN 60947-2
(4P) and rated current up to 250A .
Used to distribute electrical energy and protect lines and power equipment from damage
caused by overload, short circuit, and other faults.
This circuit breaker can be installed vertically or horizontally.
Standard:IEC/EN 60947-2
Quantity :
YeM6PV DC Molded Case Circuit Breaker (MCCB)
General
The YeM6PV DC molded case circuit breaker is used in DC distribution networks with a rated operating voltage of up to DC1000V (4P) and a rated current of up to 250A. It is used to distribute electrical energy and protect lines and power equipment from damage caused by overload, short circuits, and other faults. This circuit breaker can be installed vertically or horizontally.
Standard: IEC/EN 60947-2
Operating Conditions
- Altitude: ≤ 2000m
- Ambient air temperature: -5 °C to +40 °C
Type Designation
The YeM6PV type designation is structured as follows:
YeM6PV - 125 4P 100A DC1000
- Model:YeM6PV
- Rated current: 125, 250
- Number of poles: 2P, 3P, 4P
- Rated current options: 32A, 40A, 50A, 63A, 80A, 100A, 125A, 140A, 160A, 180A, 200A, 225A, 250A
- Working voltage: DC500, DC750, DC1000
Technical Data
| Parameter | YeM6PV-125 | YeM6PV-250 |
|---|---|---|
| Shell frame current Inm (A) | 125 | 250 |
| Number of poles (P) | 2, 3, 4 | 2, 3, 4 |
| DC working voltage (V) | 500, 750, 1000 | 500, 750, 1000 |
| Rated insulation voltage Ui (V) | DC1000 | |
| Rated impulse withstand voltage Uimp (KV) | 8 | |
| Rated current In (A) | 32A, 40A, 50A, 63A, 80A, 100A, 125A | 140A, 160A, 180A, 200A, 225A, 250A |
| Ultimate short-circuit breaking capacity Icu (KA) | 20 | |
| Running short-circuit breaking capacity Ics (KA) | Ics = 75% Icu | |
| Isolation function | Yes | |
| Tripping type | Thermal-magnetic type | |
| Electrical life (operations) | 1500 | 1000 |
| Mechanical life (operations) | 8500 | 7000 |