86-577-61989999

hymel@hymel-electric.com

Model No: YeB6PV

YeB6PV DC MCB

The rated operating voltage of YeB6PV-63 series DC miniature circuit breakers can reach DC1000V, and the rated
operating current can reach 63A, which are used for isolation, overload and short circuit protection. It is widely used in
photovoltaic system, and can also be used in industrial, civil,
communication and other DC systems to ensure the reliable
operation of systems.
Standard:IEC/EN 60947-3
Quantity :
Contact Now

YeB6PV DC Miniature Circuit Breaker

The YeB6PV-63 DC MCB is ideal for photovoltaic and industrial applications, featuring a modular design with rated voltage up to DC1500V and current up to 63A. It includes overload and short circuit protection with a breaking capacity of 6kA, compliant with IEC/EN 60947-3 standards.

Features

1.   Modular design, small size;

2.   Standard Din rail installation, convenient installation;

3.   Overload, short circuit, isolation protection function, comprehensive protection;

4.   Current up to 63A, 14 options;

5.   The breaking capacity reaches 6KA, with strong protection capacity;

6.   Complete accessories and strong expansibility;

7.   Multiple wiring methods to meet various wiring needs of customers.

YeG6PV-63 Series Circuit Breaker

YeB6PV

Frame degree roted current (A)

63

 

Pole

1P

2P

3P

4P

Ue Rated operafing voltage(V DC)

DC500V

DC1000V

DC1250V

DC1500V

Rated Current In (A)

6, 10, 16, 20, 25, 32, 40, 50, 63A

Rated insulation voltage Ui (V DC)

DC500V

DC1000V

DC1250V

DC1500V

ated Impact voltage Uimp (kV)

4

Ulimate breaking capacity lcu (kA)

6

Run breaking copacity les (%lcu)

75%Icu

Carve type

C

Trip fype

Thermal-magnetic

Mechanical

Actual average value

20000

Standard value

8500

Electric

Actual average value

2500

Standard value

1500

 

Control and indication

Shunt release(SHT)

Option

Auxiliary contoct (AX)

Alarm contact(AL)

Connection and installation

Wiring capacity  (mm²)

In≤32A, 1~25mm², l≥40A, 10~35m

Ambient temperature(°C)

-20~+70

Alfitude

≤2000m

Relative  humidity

≤95%

Pollution Level

3

Installation Environment

No obvious shock and vibration

Installation category

Class

Installation

DIN Standard rail

Dimensions(W)x(H) x(Deep)

W

18

35

54

72

H

80

80

80

80

D

71

71

71

71

Weight (kg)

0.12

0.24

0.36

0.48