86-577-61989999

hymel@hymel-electric.com

Model No: YeB6-63

YeB6-63 4.5kA 230/400V MCB

YeB6-63 miniature circuit breaker(circuit breaker) is applicable to the circuit with AC50Hz/60Hz, rated voltage of no more than 400V, rated current up to 63 A for overload protectionand short circuit protection.
This product can be applied to various places such as industrial, commercial, tall buildings, and residential houses.
Standard: IEC60898-1
Quantity :
Contact Now

YeB6-63 Miniature Circuit Breaker

General

The YeB6-63 miniature circuit breaker is applicable to circuits with AC 50Hz/60Hz, rated voltage up to 400V, and rated current up to 63A. It provides overload and short circuit protection for industrial, commercial, and residential applications.

Standard:IEC60898-1

Technical Data

ParameterValue
Rated Current (In)1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 A
Poles (P)1, 2, 3, 4
Rated Voltage (Ue)230/400 V
Insulation Voltage (Ui)500 V
Rated Frequency50/60 Hz
Breaking Capacity3000, 4500 A
Impulse Withstand Voltage (Uimp)4000 V
Dielectric Test Voltage2 kV
Pollution Degree2
Thermo-magnetic Release CharacteristicC, D

Mechanical Features

FeatureDetails
Electrical Life6000 cycles
Mechanical Life3000, 10000 cycles
Protection DegreeIP20
Reference Temperature30°C
Ambient Temperature-5°C to +40°C
Storage Temperature-25°C to +70°C

Installation

FeatureDetails
Terminal Connection TypeCable/Pin-type busbar
Terminal Size for Cable (mm²)25 mm² (AWG 18-3)
Terminal Size for Busbar (mm²)25 mm² (AWG 18-3)
Tightening Torque2 N*m (18 in-lbs)
MountingOn DIN rail EN 60715 (35mm)

Tripping Characteristics

TypeTest CurrentTripping TimeResult
B, C, D1.13 In≤ 1h (In ≤ 63A)Not tripping
B, C, D1.45 In≤ 1h (In ≤ 63A)Tripping
B3 In≤ 0.1sNot tripping
C5 In≤ 0.1sNot tripping
D10 In≤ 0.1sNot tripping

Overall and Mounting Dimensions (mm)

1P: 17.8 | 2P: 35.6 | 3P: 53.4 | 4P: 71.2

Temperature Correction

The allowable current is affected by the ambient temperature in the installation area. Reference values are provided for adjustment.